Unitised Sub Station
Get Price Quote
We are offering unitised substation are designed for locations where space and safety is a concern, population density is high, such as urban centre. Unitised substation is divided in three section or compartment – medium voltage, transformer and low voltage switchboard. Unitised substations are designed in accordance with is 14786 / iec 61330 standards with degree of protection for ip23 for transformer and ip54 for mv & lv compartments or as per customer requirement. Echnical specifications mv switchgear- 3.3 to 33 kv type of switchgear- lbs / sfu / breaker / rmu insulation medium- sf6 gas or vacuum tripping- fuse / relay short circuit rating- up to 20 ka or as per customer requirement type of cooling- oil immersed / dry type rating- 100 to 2000 kva voltage -3.3 to 33/0.433 kv or any specific phase / frequency- 3 phase / 50 or 60 hz. vector group- dyn1 or dyn5 or dyn11 or any specific. mv switchgear- acb's, mccb's current rating- up to 3250 amps voltage- 433 volts no. Of poles- 3 / 4 short circuit rating- 50ka or as per customer requirement.