    Increased power shortage and shutdown has made lift Inverters an essential factor at every place including offices, multi-storied building, manufacturing plants, shopping malls and so on. Enertech Group based in Pune and Mumbai, India offers highly reliable lift Inverters ensuring emergency rescue device for lifts usage in spite of electricity failure. The system always remains alerted to sense a power failure and starts automatically without requiring a manual start. Enertech Group a leading lift inverter suppliers in India has user-friendly, compact in size and can be tailor made to suit particular sites. Enertech lift UPS India has high capacity power generation systems that are capable of running lift/elevators, 3 phase operated critical CNC machines and many more 3 phase high power applications. When the electricity is available the Lift is directly connected to main power and only a small portion of the main supply is used for charging the storage batteries. In the event of an electricity failure, the lift inverter automatically senses the power failure and generates AC power from the batteries. This is carried out within few seconds ensuring that the lift remains without power for a few seconds only. Once the main supply is resumed, the lift is switched over to it. This cycle continues again during the next power failure. The battery bank has the capacity to stand up to 8 to 10 Hours. The common lighting load such as a staircase, parking can also be connected to the system.

    more..
  • Lift Inverter

    Lift Inverter

    Get Price Quote

    • Technology: IGBT
    • Input Voltage: 230V /415V AC (+/- 15%)
    • Input Frequency: 50 Hz (+/- 5%)
    • Output Frequency: 50 Hz (+/- 0.5%)
    • Output Voltage: 415V AC (+/- 3%)
    • Load power Factor: 0.8 to 1 lagging
    • Inverter Efficiency: > 90%
    • Output Wave form: Pure Sine Wave
    • Harmonic Distortion: Less than 3% with linear load
    • Overload: <105% continuous 105% to 200% for 30 Sec. >200% Inverter Trips
    • Battery Voltage: 72V/96V/120V/180V/240V/360V DC
    • Indications: Mains ON, Inverter ON, Battery Low, Overload, Battery Bar graph, Load Bar Graph
    • Audible Alarm: Mains Fail @15 sec Battery Low pre-alarm at 80% of discharge
    • Protections: Input single phasing / Phasing Reversal, Battery over / under voltage, output Over/ Under voltage, Output Overload, Output short circuit
    • Meter provided: Output voltage /Microprocessor based Digital LCD metering for multiple parameters
    • Changeover: Electro-mechanical / Static Switch
    • Backup time: 10 min to 10 Hours
    • Operating Temperature: 0 deg C to 50 deg C
    • Model: 6 KVA; to 100 KVA,/td>
    • Humidity: Max 95%, Non-condensing
    • Acoustic Noise: Less than 45 dB at 1 Meter